How to calculate the socket loop protection

First, the calculation conditions

Distribution voltage U e=220V

The design socket circuit adopts BV-2*.5 wire, BVR-1*2.5PE;

Check the table: RO = 8.7 ohm / KM; XO = 0.127 / KM;

The maximum distribution distance in the design plane is 50 meters, so the other circuit L=100 meters, the circuit breaker is C65 type distribution type circuit breaker, and the contact resistance RZ=1.3 milliohms;

Second, the calculation formula

Id=Ue/ZxI∑

Where Ue is the rated loop voltage and ZxI∑ is the total loop impedance

Third, protection calculation

1) Calculate ZxI∑

ZxI∑= √ (0.0013+100*0.0087)^2+(100*0.000127 ^2)
=√ 0.759+0.00016
=0.871 (Europe)

2) Calculate single-phase ground fault current Id (TN system)

Id=Ue/ZxI∑=220/0.871=253(A)

3) Checking

According to Schneider C65 miniature circuit breaker type 2 curve (distribution type), when the short-circuit current is 4-7 times of the rated current of the circuit breaker, it will act instantaneously.

The socket circuit breakers used in the design are all 065-10A/1P, ie Ie=10A;

Therefore, the single-phase ground fault current action multiple is m=Id/Ie=253/10=25.3 (times) to ensure instantaneous action, and the trip time is t=0.02 second, which fully meets the requirements of the specification.

Dry Type Distribution Transformer

Henan New Electric Power Co.,Ltd. is a comprehensive enterprise integrating product research and development, product sales, and import and export services. It has more than 45 years of research and development experience. The company has a modern workshop of more than 120,000 square meters, a research and development center, and a staff apartment of more than 30,000 square meters. The production equipment is perfect, the testing method is perfect, the technical force is strong, and the qualification is complete. We can provide high, medium and Low Voltage Transformers with voltages of 110KV and below and capacities of 120,000 kVA and below for various purposes, as well as tap changers, gas relays, oil level gauges, moisture absorbers, valves, thermometers, insulators, fans and other accessories .

Dry type transformers are widely used in local lighting, high-rise buildings, airports, terminals, CNC mechanical equipment and other places. Simply speaking, dry type transformers refer to transformers whose core and windings are not immersed in insulating oil.

Cooling methods are divided into natural air cooling (AN) and forced air cooling (AF). In case of natural air cooling, the transformer can operate continuously for a long time under rated capacity. In case of forced air cooling, the output capacity of transformer can be increased by 50%. It is applicable to intermittent overload operation or emergency overload operation; Due to the large increase of load loss and impedance voltage during overload, it is in a non economic operation state, so it should not be in a long-term continuous overload operation.

Dry Type Distribution Transformer,Non encapsulated transformer,Air Cooling Transformer,Dry Power Transformer,Dry type epoxy resin transformer

Henan New Electric Power Co.,Ltd. , https://www.newelectricpower.com